Possible faults, causes, and elimination methods of knife gate valves:
Possible faults that may occur | Reason for malfunction | Elimination methods |
Packing leakage | 1. The packing gland is not tightly pressed 2. The filling material becomes ineffective due to prolonged use or improper storage | 1. Tighten the nut evenly and tighten the packing tightly 2. Replace the packing |
Leakage between sealing surfaces | 1. There are dirt and debris adhering to the sealing surface 2. Damaged sealing surface | 1. Clean up the dirt and debris. 2. Reprocess, repair or replace |
Leakage at the connection between the valve body and the valve cover | 1. Uneven tightening of connecting bolts 2. Damaged flange sealing surface | 1. Tighten evenly 2. Reshaping |
The handwheel does not rotate flexibly or the gate cannot be opened or closed | 1. The packing is pressed too tightly 2. The valve stem nut is damaged 3. The thread of the valve stem nut is severely worn or broken 4. Valve stem bending | 1. Loosen the nut on the packing pressure plate appropriately 2. Disassemble and repair threads and remove dirt and debris 3. Replace the valve stem nut 4. Correct the valve stem |

Hidden stem knife gate valve
2023.09
pneumatic knife gate valveIt is a valve device that quickly cuts off the flow of fluid in pipelines through pneumatic systems. Its working p...
2022.01
Wear-resistant ceramic knife gate valve is a valve product with excellent performance. All contact surfaces between it and the medium are ma...
2024.04
Manual plug valve is a type of valve with a simple structure, reliable operation, and wide application. Its principle is to rotate the screw...
Contact Us
Tel: 0577-67962833
Sales: 0577-67371666
Address: Wuxing Industrial Zone, Oubei Town, Yongjia County, Wenzhou City, Zhejiang Province, China
E-mail: 412305565@qq.com