Possible faults, causes and elimination methods of knife gate valve:
possible failures | Cause of failure | Elimination method |
Packing leakage | 1. The packing gland is not pressed tightly 2. The filler fails due to long-term use or improper storage | 1. Tighten the nut evenly to compress the packing 2. Replace the packing |
Leakage between sealing surfaces | 1. There is dirt and debris attached to the sealing surface 2. Damaged sealing surface | 1. Clean the dirt and sundries 2. Rework, trim or replace |
Leakage at the connection between the valve body and the bonnet | 1. Uneven tightening of connecting bolts 2. The flange sealing surface is damaged | 1. Tighten evenly 2. Refinish |
The handwheel is inflexible or the gate cannot be opened and closed | 1. The packing is pressed too tightly 2. The stem nut is damaged 3. The thread of the stem nut is severely worn or broken 4. Stem bending | 1. Properly loosen the nut on the packing pressure plate 2. Disassemble and trim threads and remove dirt and debris 3. Replace the stem nut 4. Correct the valve stem |
2023.09
slurry valveIt is a valve used to control the flow of slurry, which has many advantages such as simple structure, reliable sealing, and easy...
2022.01
Ceramic valves mainly include ceramic gate valves, ceramic ball valves, etc. This type of valve is called the nemesis of strong corrosion an...
2023.09
pneumatic knife gate valveIt is a valve device that quickly cuts off the flow of fluid in pipelines through pneumatic systems. Its working p...
Contact Us
Tel: 0577-67962833
Sales: 0577-67371666
Address: Wuxing Industrial Zone, Oubei Town, Yongjia County, Wenzhou City, Zhejiang Province, China
E-mail: 412305565@qq.com